Waste-Heat Recovery Economizer

Efficiency

Finned-coil flue-gas heat-recovery unit that recaptures stack losses from the thermic heater — cutting fuel consumption 5–8% and paying for itself in months.

Enquire About This Product

Overview

A thermic heater firing at rated duty sends 200–300 °C flue gas up the stack; that is heat already paid for, thrown away. The economizer sits in the flue path: extended-surface finned coils intercept the exhaust and preheat the cold thermic-oil return or feed oil before it reaches the heater coil. Every degree recovered at the cold end is a degree the burner does not have to generate — typical installations recover 5–8% of fuel across the year, which in KSA gas-fired duty is a six-figure-riyal saving over a plant’s life. We design the coil around your heater’s stack dimensions and draft, supply the bypass damper for temperature control, and include the soot-blowing provisions that keep fin surfaces clean in oil-fired service.

Technical Data

Design codeASME VIII Div. 1 (coil) + structural to AISC
Coil design pressure16 barg (thermic-oil circuit)
Design temperature400 °C
Material of constructionSA-210 Gr. A1 / SA-213 T11 finned tubes; CS casing
FinsHelical or rectangular, carbon-steel, 6–12 fins/inch
Corrosion allowance1.5 mm pressure parts
TestingHydrostatic coil test, damper operation test
Insulation100–150 mm mineral wool + aluminium cladding on casing

Applications

  • Thermic heater stack heat recovery
  • Feed-oil preheating before dehydration
  • Combustion-air preheating variants

Materials & Standards

  • ASME VIII Div. 1
  • TEMA class C/CB construction conventions
  • NFPA 85 interface for burner management

Options & Variants

  • FD/ID fan compensation for added draft loss
  • Condensing tail section for maximum recovery (gas firing)
  • PLC-linked outlet temperature control